Pump Relief Valve
Chemguard can supply the pump, controller and PRV assembly as required by UL & FM as being listed orthe complete skid assembly that will include all integral piping for ILBP or Balanced pressure system.
FEATURES
- UL Tested to the latest UL 448C standard for positive displacement pumps
- FM Approved per class 1313 & 1359
- Bronze construction viton seats
- Factory set pressure @ 10% above pump's maximum design pressure
- Reseat pressure at 90% of set pressure
- Leak free at 85% of set pressure
- Factory set, labeled, and tested
- No field adjustment allowed
- Discharge must be piped back to foam concentrate tank using same pipe size as outlet or greater with no shut off valves in discharge line.